Fulton VSRT15 15HP 240 kg/hr L3 GAS MODULATING STEAM BOILER 10.34BAR
Fulton model VSRT15 L3, gas fired vertical steam boiler with Steam out put of 240 kg/hr F&A 100°C
Maximum working pressure 10.34 barg.
Requiring 16.77 m³/h of natural gas at 19 mbarg minimum pressure and 35 mbarg maximum gas pressure.
Fully modulating controls giving up to 5:1 turndown (subject to site conditions).
Supplied as standard with a Grundfos water feed pump.
Requiring an electrical supply of 400v/3ph/50hz - 14.8 A/ph (Includes burner fan motor, feedwater pump & 6A standard control unit)
The VSRT15 L3 model features / includes high integrity level limiters, auto TDS and auto bottom blowdown systems.
Minimum boiler height clearance is 2713mm
Flue outlet diameter - 6"" - Flue not included.
The automatic bottom blowdown valve incorporated within item requires compressed air at 6 Barg.
Please note all classic boilers are shipped vertically, shrink- wrapped on pallets.
Please NOTE: - Although the boiler is fitted with controls to BG01 arrangement level 3, site user will need to ensure all other aspects of BG01 requirements to ensure they have a BG01 L3 compliant steam generation system.
Manufacturers Code :
015VG040M3Description :
VSRT15 L£ Gas Modulating BoilerSKU :
368381015Tags :

| Model : VSRT 15 | ||
| A | Minimum Clearance* | 2713 |
| B | Overall Width | 1480 |
| C | Overall Depth | 1400 |
| D | Overall Height | 1939 |
| E | Boiler Height | 1868 |
| F | Boiler Diameter | 825 |
| G | Gas Inlet Height | 1868 |
| J | Safety Valve Discharge Height | 1820 |
| K | Steam Outlet Height | 1879 |
| L | Feedwater Inlet Height | 567 |
| M | Flue Outlet Height | 1094 |
| N | Flue Diameter | 150 |
| P | Main Boiler Blowdown Height | 126 |
| R | Water Level Gauge (Sight Glass) Blowdown Height | 1100 |
| S | Water Level Gauge Stand Off | 280 |
| T | Air Inlet Height | 1264 |
* Minimum height required for service & maintenance. If skid mounted an additional 200mm height required.
Note: Dimensions mm.
Note: Dimensions are approximate and only intended as a guide to aid installation.
Note: Electrical enclosures are rated IP54.
Note: Minimum flue draught.
| Brand | Fulton |
VSRT
Vertical Spiral Rib Tubeless Steam Boiler
VSRT boilers are PURE Optimised and built to last as a reliable source of clean steam, providing cost savings and operator peace of mind for years to come.
- kW rating: 100 - 1250 kW
- Output (BHP): 10 - 125 BHP
- Output (kg/h): 160 - 1956 kg/h (F&A 100°C)
- Operating Pressure: 10.34 barg
- Industry Leading Efficiencies
- Hydrogen-Ready (hydrogen-natural gas blends up to 23%)
- Smallest Footprint in the Industry
- Fully-Wetted Pressure Vessel
- 10 Year Guarantee on Pressure Vessel